CO2 Sensor Module(Telaire T6713 Series):
Telaire T6713 Series is ideal for applications where Carbon Dioxide(CO2)levels need to be measured and controlled for indoor air quality and energy saving applications, such as demand control ventilation.
All units are factory-calibrated to measure CO2 concentration levels up to 5000 ppm.
CO2 Sensor Module(Telaire T6713 Series)Features:
▪An affordable gas sensing solution for OEMs.
▪Eliminates the need for calibration in most applications with Telaire's patented ABC LogicTM software. Lifetime calibration warranty.
▪A reliable sensor design based on 20 years of engineering and manufacturing expertise.
▪Flexible CO2 sensor platform designed to interact with other microprocessor devices.
▪Small compact design allowing simple product integration.
CO2 Sensor Module(Telaire T6713 Series)Specifications:
Method |
Non Dispersive Infrared (NDIR), gold plated optics, diffusion sampling (with Telaire's Patented ABC Logic Self Calibrated Algorithm) |
|
Measurement Range(2) |
0 to 5000 ppm |
|
Dimensions |
1.18 in X 0.61 in X 0.34 in (30 mm X 15.6 mm X 8.6 mm) |
|
Accuracy(1)(5) |
400-5000 ppm+/-30ppm±3% of reading 400-2000 ppm+/-25 ppm±3% of reading |
|
Temperature Dependence |
5 ppm per℃ or 0.5% of the reading per℃, whichever is greater |
|
Stability |
< 2% of FS over life of sensor (15 years typical) |
|
Pressure Dependence |
0.13% of reading per mm Hg |
|
Calibration Interval |
Not required |
|
Response Time |
< 3 minutes for 90% step change typical |
|
Signal Update |
Every 5 seconds |
|
Warm Up Time |
▪ < 2 minutes (operational) ▪ 10 minutes (maximum accuracy) |
|
Operating Conditions |
▪ 14°F to 140°F (-10℃ to 60℃) ▪ 0 to 95% RH, non-condensing |
|
Storage Conditions |
-22°F to 158°F (-30℃ to 70℃) |
|
Output |
Digital(3) |
I2C slave up to 100kHz UART@ 19200 Baud w/Modbus support |
PWM Output Mode |
Two options: ▪ Cycle period 1002 ms(-1Hz) ▪ 40 us (25kHz) |
|
Power Supply Requirements(4) |
▪ 4.5-5.5 VDC ▪ Peak200mA(155mAtypical) ▪ Average 25mA(20mAtypical) |
|
Interface Connections |
Designed for six (6) pin male header with 0.1 in(2.54 mm)spacing.Header not included. |
Notes:
(1) Tolerance based on span gas of ±2%,which adds to the uncertainty, tested at Standard Ambient Temperature and Pressure (SATP).
(2) Subjecting sensors to environments less than 400 ppm for more than 15 minutes may affect accuracy due to ABC Logic algorithm.
(3) Please call for detailed product specifications.
(4) Based on nominal 5VDC input voltage. For best performance, DC supply should be a regulated, low noise power source.
(5) The module may exhibit a tolerance addition of ±6Oppm when first installed. This wil be corrected by the ABC Logic in first weeks of operation.
If you cannot find what you want, you can entrust OFweek to source for you. Just click:
Sourcing ServiceRecommended Products
-
P-type Metal Oxide Carbon Monoxide (CO) Sensor
-
P-type Metal Oxide VOC Sensor
-
Pre-calibrated module for combustible gas
-
Compact CO Sensor
-
15x15 Indoor Air Quality Sensor 100 ppm C Package 110-802
-
P-type Metal Oxide Carbon Monoxide (CO) Sensor
-
P-type Metal Oxide VOC Sensor
-
Carbon dioxide (CO2) sensor module
-
Gas sensor KSIM 1260 for detection of Sulfur Hexafluoride SF6
-
Thermal Conductivity Sensor for Leak or Pressure Detection