• Temperature range (scalable via software): -30 - 900°C​
• Spectral range: 8 -14µm​
• Optical resolution: 22:1​
• CF-Optics (optional): 0.6mm @10 mm​
• Outputs/analog: 4 - 20 mA​
• Environmental rating: IP 65 (NEMA-4)​
• Ambient temperature: -20 - 75°C​
• Relative humidity: 10-95%, non condensing​

  • Model Number: PSC-CX
  • Data Sheet: Date Sheet File
Quantity:
- +

Product Specification

PSC-CX
Digital, two wire, loop powered infrared temperature sensor for OEM applications

PSC-CX Infrared Temperature Sensor Description
The PSC-CS self-Contained, 2-wire loop powered IR temperature sensor with 4-20 mA output features:
• High-performance, great value
• Simple 2-wire installation
• Wide range of -30°C to 900°C (adjustable with PSC Connect Software)
• Optical resolution of 22:1
• Optional USB programming interface
• Alarm output (0-30 V / 500 mA)
• Real-time 2-wire output and digital communication
• Versatile power requirements: 5-30 VDC

PSC-CX Infrared Temperature Sensor Specifications

General Specifications
Environmental rating
IP 65 (NEMA-4)
Ambient temperature
-20 - 75°C
Storage temperature
sensing head: -40 - 85°C
Relative humidity
10-95%, non condensing
Vibration
IEC 68-2-6: 3 G, 11-200 Hz, any axis
Shock
IEC 68-2-27: 50 G, 11ms, any axis
Weight
350 g
Electrical Specifications
Outputs/analog
4 - 20 mA
Output/Alarm
0-30 V/ 500 mA (open collector)
Outputs/digital (optional)
USB
Loop impedances
max. 1000 Ω 
Cable length
8 m
Power supply
5 - 30 V DC
Measurement Specifications
Temperature range (scalable via software)
-30 - 900°C
Spectral range
8 -14µm
Optical resolution
22:1
CF-Optics (optional)
0.6mm @10 mm
System accuracy (at ambient temperature 
23±5°C and object temperture >20°C)
±1% or ±1.4°C 
Repeatability (at ambient temperature
23 ±5°C and object temperture >20°C)
±0.5% or ±0.7°C
Temperature resolution
0.1°C
Exposure time (90% signal)
150ms
Emissivity/Amplification (adjustable via soft-ware)
0.100 - 1.100
Transmissivity (adjustable via software)
0.100 - 1.000
Signal processing (parameter adjustable
only via softwre)
peak hold, valley hold, average; extended hold
function with threshold and hysteresis