Carbon Dioxide (CO2) Gas Controller - F2000TSM-CO2-PID

  • Carbon Dioxide (CO2) Gas Controller
  • Carbon Dioxide (CO2) Gas Controller
Mouse over image to zoom

​• CO2 measuring range​: 0~2,000ppm/0~5,000ppm optional
​• Accuracy @25°C(77°F): ±40ppm + 3% reading​
​• Stability​: <2% of FS over life of sensor
​• Response time​: <2 minutes for 90% step change​
​• Power supply​: 24VAC/24VDC​
​• Consumption​: 1.5 W max. ; 0.8 W avg.​
​• Operation temperature: 0~50°C(32~122°F)
​• Operation humidity​: 0~95%RH, non condensing​

  • Model Number: F2000TSM-CO2-PID
  • Data Sheet: Date Sheet File
Quantity:
- +

Product Specification

Carbon Dioxide Controller
Model: F2000TSM-CO2-PID
CE Approval


F2000TSM-CO2-PID Carbon Dioxide Controller Features
• Real-time CO2 detection
• NDIR infrared CO2 module with self-calibration and more than 10 years lifetime
• Optional 6 LED lights indicating CO2 ranges
• One 0~10VDC or 2~10VDC output
• PID output for a VAV terminal with the setpoint of the minimum opening
• Linear output available for CO2 measurements
• Optional Modbus RS485 interface
• Four CO2 setpoints selectable via jumpers for PID output
• The minimum opening can be set via RS485
• Application for ventilation systems, BAS and single fan control etc.
• Smart structure and easy mounting
• CE-Approval


F2000TSM-CO2-PID Carbon Dioxide Controller Specifications

Gas detected
Carbon Dioxide (CO2)
Sensing element
Non-Dispersive Infrared Detector (NDIR)
Accuracy @25°C(77°F), 2000ppm
±40ppm + 3% reading
Stability
<2% of FS over life of sensor (15 yr typical)
Calibration interval
ABC Logic Self Calibration System
Response time
<2 minutes for 90% step change
Warm up time
2 hours (first time)
2 minutes (operation)
CO2 measuring range
0~2,000ppm (default)
0~5,000ppm available
CO2 Sensor life
More than 10 years
Power supply
24VAC/24VDC
Consumption
1.5 W max. ; 0.8 W avg.
Analog output
0~10VDC or 2~10VDC selectable by the jumper
Output select
PID control output or Linear output for CO2 measurement selectable via jumpers
Minimum opening
2V default and can be preset via RS485
Setpoints
Provide 4 CO2 setpoints for PID control:
CO2≥ 600ppm; CO2≥800ppm; CO2≥1000ppm(default); CO2≥1200ppm;
Selected by jumpers
Modbus interface
Modbus RS485 interface, 19200bps, 15KV antistatic protection.
6 LED lights
From left to right:
Green/Green/Yellow/Yellow/Red/Red
1st green light on as CO2 measurement ≤600ppm
1st and 2nd green lights on as CO2 measurement >600ppm and ≤800ppm
1st yellow light on as CO2 measurement >800ppm and ≤1,200ppm
1st and 2nd yellow lights on as CO2 measurement >1,200ppm and ≤1,400ppm
1st red light on as CO2 measurement >1,400ppm and ≤1,600ppm
1st and 2nd red lights on as CO2 measurement >1,600ppm
Operation conditions
0~50°C(32~122°F); 0~95%RH, non condensing
Storage conditions
0~60°C(32~140°F)/0~80%RH
Net weight
180g
Dimensions
100mm x 80mm x 28mm
Installation standard
65mm x 65mm or 2" x 4" wire box
Approval
CE-Approval


F2000TSM-CO2-PID 
Carbon Dioxide Controller 
Models Guide

Type
Model
Description
CO2 PID Controller
F2000TSM-CO2-S100-PID-02/05
1X analog output with PID (linear output selectable),
CO2 range: 0~2,000ppm/0~5,000ppm
F2000TSM-CO2-S101-PID-02/05
1X analog output with PID (linear output selectable),
Modbus interface.
CO2 range: 0~2,000ppm/0~5,000ppm
F2000TSM-CO2-L100-PID-02/05
6 LED lights indicates CO2 ranges.
1X analog output with PID (linear output selectable),
CO2 range: 0~2,000ppm/0~5,000ppm
F2000TSM-CO2-L101-PID-02/05
6 LED lights indicates CO2 ranges.
1X analog output with PID (linear output selectable),
Modbus interface.
CO2 range: 0~2,000ppm/0~5,000ppm


If you cannot find what you want, you can entrust OFweek to source for you. Just click:

Sourcing Service