• Humidity Range: 0~100%RH
• Temperature Range: 0°C~50°C
• AC power supply: AC 24V (18V~24V)
• Humidity Accuracy: ± 3%RH (5~95%RH, 25°C​)
• Temperature Accuracy: ± 0.5°C (25°C)
• Working Humidity: 0~100%RH (no condensation)
• Working Temperature: -10℃~60°C
• Response time: ≤15s (1m/sair speed)

  • Model Number: JWSL-6
Quantity:
- +

Product Specification

JWSL-6 Protective Temperature and Humidity Transmitter Introduction
Sensor, transmitter integrated design and big screen display is suitable for hvac indoor environment temperature and humidity measurement. It uses special temperature compensation circuit and linearized processing circuit. This product has reliable performance, long service life, fast response speed. A variety of models meet the requirement of RoHS lead-free.

JWSL-6 Protective Temperature and Humidity Transmitter Characteristic
• Low price
• Low drift
• Fast response
• Strong anti-interference
• Easy installation
• Stable performance
• Long service life
• Many kind of analog output signal
• Special filter design, can effectively reduce measurement error from the wind speed , prolong probe's service life

JWSL-6 Protective Temperature and Humidity Transmitter Parameters

DC power supply Current output: DC 24V (22V~26V)
Voltage output: DC 24V (12V~24V)
Net output: DC 24V (12V~24V)
AC power supply AC 24V (18V~24V)
Max current Two wires system output: 40mA (DC 24V)
Three wires system output: 50mA (DC 24V)
Voltage output: 20mA (DC 24V)
Net output: 20mA (DC 24V)
Accuracy Humidity: ±3%RH (5~95%RH, 25°C)
Temperature: ± 0.5°C (25°C)
Working environment Humidity: 0~100%RH (no condensation)
Temperature: -10℃~60°C
Range Humidity: 0~100%RH
Temperature: 0°C~50°C
Response time ≤15s (1m/sair speed)
Long-term stability Humidity: ≤ 1%RH/y
Temperature: ≤ 0.1℃/y
Output signal Current output: 4~20mA
Voltage output: 0~5V
Net output: RS485/RS232
Load capacity Voltage output: output impedance ≤ 250Ω
Current output: ≤ 500Ω
Installation Wall mounted fixed on the wall
Pipe type flange or thread installation (thread M22x1.5)
Shell ABS white 117mm x 86mm x 41mm (without probe)