Combustible Gas Sensor - 4P-75C CiTipeL

  • Combustible Gas Sensor
Mouse over image to zoom

• Operating Principle: Catalytic Oxidation
• Gases Detected: Combustible gases
• Range: 0-100% LEL
• Sensitivity: 24 ± 4 mV/%methane
• T90 Response Time: <20 seconds (methane)
• Linearity: Linear up to 3% methane
• Operating Voltage: 3.0 ± 0.02 VDC
• Operating Temperature Range: -20°C to +55°C
• Operating Humidity Range: 0-90% RH non-condensing

  • Model Number: 4P-75C CiTipeL
  • Data Sheet: Date Sheet File
Quantity:
- +

Product Specification

4P-75C CiTipeL Combustible Gas Sensor Key Features & Benefits:
• ATEX, UL and CSA Approvals
• Withstands EN/IEC 60079-0 impact test
• Enhanced H2S and silicone poison resistance

4P-75C CiTipeL Combustible Gas Sensor Performance Characteristics

MEASUREMENT
Operating Principle Catalytic Oxidation
Gases Detected Combustible gases
Suitable for Methane, ethane, propane, butane, pentane, hexane, 
carbon monoxide & hydrogen
Unsuitable for Higher hydrocarbons, alcohols, ketones, esters, hydrogen sulfide 
and other sulfur containing compounds
Range 0-100% LEL
Sensitivity* 24 ± 4 mV/%methane
T90 Response Time* <20 seconds (methane)
Poison Resistance Resistance to H2S poisoning
Superior silicone resistance
H2S Filter Lifetime Typically 1000 ppm hr
Linearity Linear up to 3% methane
ELECTRICAL
Operating Voltage 3.0 ± 0.02 VDC
Detector Operating Current 75 ± 7 mA
Maximum Power Consumption 263 mW
Resolution 1% LEL
MECHANICAL
Casing Material Stainless steel 316
Pin Material Gold plated brass
Weight 24 g (nominal)
Orientation Sensitivity None
ENVIRONMENTAL
Operating Temperature Range -20°C to +55°C
Operating Pressure Range 1 atm ± 20%
Operating Humidity Range 0-90% RH non-condensing
LIFETIME
Long Term Span Drift* <5% signal/month
Long Term Zero Drift* <5% LEL methane /month
Recommended Storage Temp 0°C to 20°C
Shelf life 6 months in sealed container
Warranty 12 months from date of despatch

* Specifications are valid at 20°C, 50%RH and 1013 mbar at a flow rate of 300 ml/min. Performance characteristics outline the performance of sensors supplied within the first 3 months. Output signal can drift below the lower limit over time.