AQ-Alert+ Air Quality Monitor - AQM Series
• Supply voltage: 24Vdc ± 20%
• Current consumption: 250mA max
• Up to 3 analogue – voltage and/or current
• RS232 or RS485 (Modbus RTU)
• Up to 3 relays
• LEDs
• Buzzer
- Quantity:
- - +
Product Specification
AQ-Alert+
Air Quality Monitor
The AQ-Alert+ is designed to monitor and control indoor air quality in the home, workplace and public areas, resulting in benefits such as improved comfort and health.
While most customers chose a monitor from our range of standard products, the configuration of the AQ-Alert+ may be defined by the user, making it ideally suited for use in a wide range of applications with varying requirements.
The AQ-Alert+ can be fitted with up to five different sensors and a variety of audio, visual, analogue, communications and relay outputs.
With the appropriate configuration, the AQ-Alert+ can operate in the following modes:
Stand Alone
The AQ-Alert+ monitors the air quality and alerts the occupant when a change in room conditions occurs.
Direct Control
The AQ-Alert+ monitors the air quality and directly controls ventilation, heating or air conditioning in order to maintain a preset range of room conditions. This can be via relays or analogue outputs.
Integration into a Building Management System
The AQ-Alert+ sends air quality information to another system that controls ventilation, heating or air-conditioning. Multiple units can be individually configured and used throughout an entire system.
Sensor Options
• Carbon dioxide
• Oxygen
• Temperature
• Relative humidity
• Atmospheric pressure
Applications
• Schools
• Offices
• Homes
• Public buildings
Output Options
• Up to 3 analogue – voltage and/or current
• RS232 or RS485 (Modbus RTU)
• Up to 3 relays
• LEDs
• Buzzer
Certified Standards
• EN50270:2006,
• RoHS compliant
Table 1 Maximum ratings
Parameter |
Maximum ratings |
Description |
Supply voltage |
24Vdc ± 20% |
Optional mains adaptor available |
Current consumption |
250mA max |
All possible sensor and output options fitted |
Table 2 Sensor options and parameters
Sensor |
Symbol |
Range |
Units |
Description |
Carbon dioxide |
CO2 |
0 - 5000
0 - 10 000
|
ppm |
Accuracy: ±70ppm, ±5% of reading (whichever is greater) Resolution: 1ppm |
Oxygen |
O2 |
0 - 25 |
% |
Accuracy: ±1% vol.O 2 (after calibration in fresh air) Resolution: 0.01% vol.O2 |
Temperature |
T |
0 - 50 |
°C |
Accuracy: ±2°C Resolution: 0.1°C |
Relative humidity |
Rh |
0 - 95 |
%Rh |
Non-condensing Accuracy: ±3% Resolution: 0.1% |
Atmospheric pressure |
P |
750 - 1150 |
mbar |
Accuracy: ±5mbar Resolution: 1mbar |
Table 3 Output options and parameters
Output |
Number |
Options |
Description |
Analogue (current or voltage) |
3 |
4 - 20mA 0 - 5Vdc 0 - 10Vdc 1 - 5Vdc |
For current output, maximum load = 500Ω. For voltage output, minimum load = 10kΩ. Output range is directly proportional to the relevant sensor’s measuring range |
Digital communications |
1 |
RS232 RS485 |
Modbus RTU protocol For RS485, up to 32 devices on the same bus |
Relay |
3 |
37.5VA, 250Vac max |
All three relays switch a common input Individual configurable switch points Standard hysteresis = 1% of the set switch point Normally open (NO) operation, user defines the sensor range/s when the relays are closed |
LEDs |
1 |
Traffic light warning sequence |
Red, amber and green LEDs Configurable sensor activation thresholds Standard hysteresis = 1% of the set threshold Continuous and/or intermittent operation |
Buzzer |
1 |
70dB @ 4kHz |
Configurable sensor alarm thresholds Standard hysteresis = 1% of the set threshold Continuous and/or intermittent operation |
PART NUMBERING SYSTEM
Generate your specific part number using the system in Figure 1. Use only those letters and numbers that correspond to the sensor and output options that you need – omit those that you do not. Include ‘AQM-‘at the beginning of the part number. The configuration reference number defines how your customised AQ-Alert+ will behave and is allocated by SST.
If you cannot find what you want, you can entrust OFweek to source for you. Just click:
Sourcing ServiceRecommended Products
-
CO Gas Alarm for CO Detection
-
Combustible, Explosive and Toxic Gas Leak Alarm
-
Natural Gas, CO Leakage Detection with Plug
-
Battery-operated CO Alarm With LCD Display; Comply with EN50291
-
Venus Carbon Monoxide Alarm, Battery-opearated CO Alarm
-
Combustible Gas Alarm with EN50194 Approval
-
Gas Alarm for Combustible Gas and CO Detection
-
Back Plug-in Detector for LPG, Natural Gas and Carbon Monoxide
-
LPG, Natural Gas, CO Gas Alarm
-
Gas Alarm System for Detecting Leakage of CO, CombustibLe Gas and Aether