Alarm Processor Gas Alarm Signal Processing - 9927
Dimensions: 19.0" W x 5-1/4" H x 9.0" D
Power: 110/220 VAC 50/60 Hz, 15W
Input Channels: 8
Alarm Input Per Channels: 3
Summary Relays: 3 (Warn, Alarm, Malfunction)
Relay Contacts: 2C (DPDT) for each, 2A resistive at 22V AC
- Model Number: 9927
- Quantity:
- - +
Product Specification
Model 9927 Alarm Processor:
Accepts eight channels of alarm contacts; three alarms for Low, High and Malfunction conditions per channel.
There are three summary relays, one for each alarm level, an audible buzzer and an Acknowledge push button switch. It functions as a typical annunciator sequence per Instrument Society of America Sequence A, automatic reset, as described below:
Sequence State | Ack Switch | Visual Display | Audible Alarm |
Normal | None | OFF | OFF |
Alarm | None | Flashing | Audible |
Acknowledge | Acknowledge | On | Silent |
Normal | None | Off | Silent |
The 9927 provides a locking key switch that permits calibration and testing without causing an audible alarm. Appropriate input terminals are provided to permit a connection to a battery power backup source.
9927 Specifications
Dimensions:
19.0" W x 5-1/4" H x 9.0" D
Weight:
Power:
110/220 VAC 50/60 Hz, 15W
Input Channels:
8
Alarm Input Per Channels:
3
Summary Relays:
3 (Warn, Alarm, Malfunction)
Relay Operating Mode:
Failsafe-loss of power or input connection will de-energize relay to the alarm state condition
Relay Contacts:
2C (DPDT) for each, 2A resistive at 22V AC
Relay Disable:
Keyswitch (for calibration, etc.). LED flashes to warn of disable condition
Audible Alarm:
Pulsating audible tone for any Warn, Alarm, or Malfunction until the Acknowledge switch is pressed
Acknowledge:
Operator push-button switch will acknowledge all alarm conditions, restoring relays to non-alarm state, silencing the audible alarm, and changing the status LED alarm indicator from flash to steady until alarm condition ceases
If you cannot find what you want, you can entrust OFweek to source for you. Just click:
Sourcing ServiceRecommended Products
-
CO Gas Alarm for CO Detection
-
Combustible, Explosive and Toxic Gas Leak Alarm
-
Natural Gas, CO Leakage Detection with Plug
-
Battery-operated CO Alarm With LCD Display; Comply with EN50291
-
Venus Carbon Monoxide Alarm, Battery-opearated CO Alarm
-
Combustible Gas Alarm with EN50194 Approval
-
Gas Alarm for Combustible Gas and CO Detection
-
Back Plug-in Detector for LPG, Natural Gas and Carbon Monoxide
-
LPG, Natural Gas, CO Gas Alarm
-
Gas Alarm System for Detecting Leakage of CO, CombustibLe Gas and Aether