Differential Pressure Manometer & Flow Meter
-
Price
Price on request ≥1piece
-
Model Number
DT-8897/8897H -
Data Sheet
-
Package
Original packaging -
Specs
DT-8897/8897H -
Quantity
- +Send Inquiry
Find Similar Products
Product Description
• DT-8897/8897H measures Gauge/Differential Pressure, Air Velocity, Air Flow and temperature.
• Hot wire anemometer(8897H) .
• Large LCD display with backlight.
• Relative time clock on MAX MIN and AVG provides a time reference for measurement.
• Pressure measurement provides Zero Adjust and DIF function.
• Display Pressure, Air Velocity or Air Flow plus Temperature simultaneously.
• Easy to set Area dimension (up to 8 point).
• USB interface, USB to UART Bridge Controller.
• Low battery indication, and Auto Power Off mode (Sleep mode) increases battery life.
DT-8897/8897H Differential Pressure Manometer Specifications
Accuracy |
±0.3%FSO |
|
Repeatability |
±0.2% (Max.+/ -0.5% FSO) |
|
Linearity/Hysteresis |
±0.29% FSO |
|
Pressure Range |
±2psi (±55.40 inH2O) |
|
|
Units |
Range/Resolution |
Units and Resolution |
psi |
2.000/0.001 |
mbar |
137.8/0.1 |
|
kPa |
13.78/0.01 |
|
inHg |
4.072/0.001 |
|
mmHg |
103.4/0.1 |
Size(HxWxD): 210mm x 75mm x 50mm
Weight: 280g
DT-8897/8897H Flow Meter Specifications
Air Velocity |
Range |
Resolution |
Basic Accuracy |
8897 |
8897H |
m/s(meter per second) |
0.40~30.00 |
0.01 |
±3% ± 0.20m/s |
* |
|
0.1~25.0 |
0.01 |
±5% ± 1m/s |
|
* |
|
ft/min(feet per minute) |
80~5900 |
1 |
±3% ± 40ft/min |
* |
|
20~4925 |
1 |
±5% ± 1ft/min |
|
* |
|
km/h(kilometers per hour) |
1.4~108.0 |
0.1 |
±3% ± 0.8km/h |
* |
|
0.3~90.0 |
0.1 |
±5% ± 1km/h |
|
* |
|
MPH(miles per hour) |
0.9~67.0 |
0.1 |
±3% ± 0.4MPH |
* |
|
0.2~55.8 |
0.1 |
±5% ±1 MPH |
|
* |
|
Knots(nautical miles per hour) |
0.8~58.0 |
0.1 |
±3% ± 0.4knots |
* |
|
0.2~48.5 |
0.1 |
±5% ± 1knots |
|
* |
|
Temperature °C |
0 to 50.0°C |
0.1 |
±1.0°C |
* |
* |
Temperature °F |
32.0 to 120.0°F |
0.1 |
±2.0°F |
* |
* |
Air Flow |
Range |
Resolution |
Area |
* |
* |
CFM (CFM=ft3/min) |
0-999,900ft3/min |
0.001~100 |
0-999.9 ft2 |
* |
* |
CMM (CMM=m3/min) |
0-999,900m3/min |
0.001~100 |
0-999.9 m2 |
* |
* |