Product Specifications/Features
    YOKOGAWA Analog Input Module AAI143


    STANDARD SPECIFICATIONS of AAI143
    Current/Voltage Input Modules (Non-Isolated)
    These modules provide 16 inputs of mainly 4 to 20 mA DC or 1 to 5 V DC standardized signals from 2-wire/4-wire transmitters.
    They can be used in dual-redundant configuration.


    Current Input Modules (Isolated)
    AAI143 provides 16 inputs of 4 to 20 mA signal. It can be used in dual-redundant configuration.

    Items Specifications
    Model AAI143 (*1)
    Number of input channels 16, isolated
    Input signal 4 to 20 mA
    Allowable input current 24 mA
    Input resistance Power ON 270 Ω (20 mA) to 350 Ω (4 mA) (*2)

    Power OFF 500 kΩ or larger
    Accuracy ±16 μA
    Data update period 10 ms
    Transmitter power supply 19.0 V or higher (at 20 mA) 25.5 V or less (at 0 mA) (output current limit: 25 mA) (*5)
    Setting of 2-wire or 4-wire transmitter For each channel by setting pin
    Drift due to ambient temperature change ±16 μA/10 C
    Maximum current consumption 230 mA (5 V DC), 540 mA (24 V DC)
    Weight 0.3 kg
    External communication Pressure clamp terminal, MIL connector Cable, dedicated cable (KS1)
    HART communication (*3) Available



    *1: A Zener barrier is not allowed to be connected with this module. Use an isolation barrier when the module is used in
    intrinsically safe application.
    *2: The module input resistance viewed from the terminals depends on the current strength as calculated as below:
    250 Ω +
    current value
    voltage drop in the input protection circuit
    F04E.ai
    *3: When this module is installed to a ER bus node unit with HART function, the EB401 firmware must be rev. 2 or later.
    *4: When the dedicated cable is used, the withstanding voltage is 500 V AC (between the input signal and the system). When
    the ML connector cable is used, the withstanding voltage depends on the electrical specifications of the cable.
    *5: This voltage is generated between the connecting terminals for 2-wire transmitters for this module. When calculating the
    minimum operating voltage for transmitters, consider to allow margins for voltage drop in external wiring.

Click here to send inquiry
Didn't find what you're looking for? Post a Buy Offer
Send inquiry directly to this supplier
Vicky Hu
Ms. Vicky Hu
 
From: vicky@whxyauto.com(Not you?)

Enter your inquiry details such as:

  • Self introduction
  • Required specifications
  • Inquire about price/ MOQ
View sample
  - Enter between 20 to 3,000 characters, English only.
   
More products from this companyFind More Products
Find Similar Products By Category
Related Searches

Product Index

Company Profile